Condenser fan control stabilizes condensing pressure within target range, guarantee expansion valve liquid supply and system stability. Common control modes: single pressure switch step control, dual speed fan stage control, EC fan continuous variable speed. EC fan variable speed is the most energy-saving solution; fan speed follows condensing pressure signal 4–20mA. Low ambient winter risk: condensing pressure drops too low, liquid supply pressure insufficient, expansion valve cannot feed refrigerant normally. Low ambient protection measures: fan cycle control, air damper shutter, condenser flooding method, split condenser isolation. Air damper shutter closes automatically when pressure too low, reduce air flow to keep condensing pressure from collapsing. Condenser flooding: store excess refrigerant inside condenser coil to reduce effective heat exchange area for pressure lifting. Xiteliduo low temperature export rack configures fan stage control + air shutter for cold climate zone as option. Flooding method needs extra refrigerant charge and receiver volume; not suitable for systems with limited refrigerant allowance. Refrigeration maintenance & repair company sets condensing pressure target according to refrigerant type and design temperature.