Air curtain creates invisible air isolation at cold room door opening, reduces hot humid air infiltration, cuts frost generation on air cooler. Two mainstream types: centrifugal air curtain and cross flow air curtain; centrifugal type has stronger wind pressure, used for low temp and big door. Cross flow air curtain is quieter, low cost, suitable for medium temperature fresh cold room with small swing door. Installation rule: air curtain mounted directly above door opening, airflow slightly inclines toward outside (5~10°), enhance isolation effect. Wind speed selection: medium temp cold room ≥5m/s; frozen cold room ≥8m/s; blast freezer ≥10m/s. Xiteliduo air curtain matched with cold room door supports 380V export voltage, optional EC fan energy saving model. Air curtain only works when door opens; interlock with door switch to stop fan after door closes, save power. Improper installation angle (blow inward) will push cold air out of cold room and increase refrigeration load reversely. Air curtain cannot replace door sealing; it is auxiliary isolation measure, cannot work if door stays open for long time. Refrigeration maintenance & repair company checks air curtain wind direction and fan balance when cold room frost frequency rises obviously.