Machine Room Commissioning, Start-up Sequence, Acceptance Checklist & Operation Log

Machine room commissioning is the final verification of the whole refrigeration system after installation, before formal handover. Standard start-up sequence: visual inspection → leak test → vacuum → refrigerant charging → oil check → single component test → load running. Leak test: pressurize with dry nitrogen, hold pressure and detect leak; vacuum target below 500 microns for POE oil system. Charging: charge liquid refrigerant into receiver side; never charge liquid directly into compressor suction port. Commissioning key parameters: superheat, subcooling, condensing pressure, suction pressure, oil level, defrost termination temperature. Xiteliduo provides commissioning checklist, operation manual and alarm troubleshooting document together with equipment. Acceptance items: temperature stability, pull-down time, running current, noise, vibration, all alarm function test. Operation log record: daily room temperature, pressure, ambient temperature, running hour, alarm event and maintenance action. Training for end user: normal operation, alarm judgment, forbidden operation, safe pump down procedure and refrigerant handling. Handover standard: all test data recorded, drawings updated as-built, spare parts list submitted. Refrigeration maintenance & repair company recommends 72 hours continuous load running test before final acceptance.

FAQ

  1. What is the correct order before refrigerant charging? Pressure leak test and vacuum pumping.
  2. What is the vacuum target for POE oil system? Below 500 microns.
  3. Where to charge liquid refrigerant? Receiver side.
  4. What core parameters need recording during commissioning? Superheat, subcooling, suction and condensing pressure.
  5. How long is the suggested continuous load test? 72 hours.
  6. What log content should be recorded daily? Temperature, pressure, running hours and alarms.
  7. What must be tested before acceptance? All protection and alarm functions.
  8. What document should be handed over to customer? As-built drawing, manual, checklist and spare part list.
この記事のURL: https://ja.xtldcool.com/news/835.html

オンラインで製品のカスタマイズプランを入手する

以下の欄に必要事項をご記入いただければ、無料で入手できます。

相談ホットライン

+86-18157593311

Xiteliduo & Chuanli

R32半密閉型ピストンコンプレッサーおよびカスタムメイドのターンキー式産業用冷凍システムの中国直営工場。自社開発のコンプレッサーと包括的な冷凍ソリューションにより、熱帯地域や極低温の動作環境においても安定した性能を発揮します。

お問い合わせ

技術サービス:+86-575-83665888;83068555 
コンプレッサーホットライン:+86-18157593311 
電気ヒーターチューブホットライン:+86-13857577938 
Eメール:helenliu1983xtld@gmail.com 
電気加熱管工場:紹興市嵊州市甘林鎮東湖村150号 
コンプレッサー工場:紹興市嵊州市東国経済開発区679号

Copyright © 2026 浙江西特利多環境技術有限公司および嵊州市川利環境技術有限公司。無断転載・複製を禁じます。