Refrigerant pipeline includes discharge line, liquid line, suction line; improper sizing causes excessive pressure drop and poor oil return. Suction line design is the most critical: pressure drop directly reduces compressor capacity, slope toward compressor for oil return. Standard oil return slope for suction pipe: 0.5–1% downward gradient to compressor; horizontal pipe cannot level or reverse slope. Vertical suction riser needs oil trap (U trap) for low speed oil carry; single riser over 3m must design oil trap. Liquid line pressure drop control: avoid flash gas before expansion valve; flash gas reduces effective cooling capacity severely. Xiteliduo pipeline adopts seamless copper tube for fluorine refrigerant, stainless steel pipe for high pressure CO₂ system. Pipe support: use thermal isolation hanger for cold suction line, prevent heat bridge and condensation dripping on building structure. Suction line insulation: closed cell rubber foam insulation, vapor barrier jacket to stop moisture penetration and ice formation. Different circuit pipes mark color and tag: red discharge, blue suction, green liquid line for easy identification. Refrigeration maintenance & repair company checks oil trap and slope after long time running, avoid oil logging in low point.